Asenware AW-D102 is an intelligent rate of rise heat detector that can be integrated with the Asenware AW-FP100 Series Addressable Fire Alarm Control Panel. Each device can be assigned a specific ID, allowing the panel to continuously monitor a particular detector location. This reduces maintenance costs and simplifies system upkeep.
• Addressable-analog communication
• Rate-of-rise feature activates when ambient temperature increases at the rate of 7.1 ℃/5S
• Low Standby current
• Two-wire connection
• Two LEDs (RED), blinks in normal condition and becomes stationary during fire alarm condition.
• Remote test from Panel
Spacing
Spacing of detector must be followed by standard EN 54 or NFPA 72. N FPA 72
suggests for low airflow application spacing of 9.1 m for ceiling height up to 3.15 m can
be applicable. However, please follow the specific codes and local codes for specific
applications.